Zio Inc Datacenter

Facility Specifications:

The total underground facility measures 570,000 square feet. There are two entrances/exits and three additional emergency exits, all of which are secured and monitored.

The facility is very secure. The overall underground has limited and monitored access. Each building will be a stand-alone facility with its customized security system. Each building will be protected from tornado and windstorms, flooding, lightning and earthquakes. The underground is located 260 feet above the Ohio River, the nearest major water source.

Ceiling heights in the underground are ideal for data center buildings. The underground ceiling height is 24 feet. After the six-foot gap for the fresh air plenum and floor/ceiling thickness, each building will have at least 14 feet concrete floor to concrete ceiling heights, unless the tenant specifies less.

Diesel generators back up the entire power network. The generators are in an underground building, protected from the elements, but also have remote mounted radiators near an outside opening for ventilation purposes. The generator building is also under constant surveillance by camera and has alarm points at its entryways.

The underground generator and fuel storage area is designed to support 24 megawatts of generator capacity and 125,000 gallons of fuel storage. The first two 2.25-MW Caterpillar generators are already in place.

The master plan allows for a second underground generator facility that can provide an additional 24 megawatts of backup power.?

Facility Infrastructure:

As you know, reliable, redundant infrastructure is a must for any significant data center. The Facility has properly designed and installed the necessary infrastructure with that in mind.

Power - Currently the facility has 4 megawatts of power capacity. In addition, the company has approval to build a 40-MW onsite substation. If more power is desired the local utility is prepared to increase capacity. All power will be backed up with generators located within the underground facility.

Fiber - Multiple fiber providers serve the Louisville market. AT&T and Insight Communications have fiber installed at The Facility. Other fiber providers, including Level 3 Communications, Time Warner Cable and Kentucky Data Link (KDL), are also available.

Grounding - The Facility has an extensive grounding system, using five-hundred (500) grounding rods. The rods are 5/8" x 8'0" copper clad rods. The rods are inserted into 3" diameter holes with earth enhancement material (Erico Part #GEM 25A) packed around the rod. The GEM material is 20 times lower in resistance than bentonite clay. The rods are connected with 4/0 copper stranded wire that is exothermally welded to the tops of all 500 rods, forming a grounding grid throughout the entire facility. The system creates a low impedance grounding grid to protect data equipment. The grounding grid is in full agreement with IEEE Std. 1100 - 1990 and will provide 2 ohms of resistance or less.

Backup Power?- Diesel generators back up the entire power network. The generators are in an underground building, protected from the elements, but also have remote-mounted radiators near an outside opening for ventilation purposes. The generator building is also under constant surveillance by camera and has alarm points at its entryways. The underground generator and fuel storage area is designed to support 24 megawatts of generator capacity and 125,000 gallons of fuel storage. The first two 2.25-MW Caterpillar generators are already in place.

Maintenance contracts are in place with a local distributor and Caterpillar factory- trained mechanics.?

Fuel Supply (Backup Power) - The generator farm is supplied with fuel from our underground diesel fuel supply and is housed in a separate underground building. Two suppliers and two trucking companies maintain?the fuel system. This gives us flexible access to fuel delivery. Fuel is delivered from the outside so that no fuel trucks come into the underground facility. The facility fuel farm is located underground and will consist of five?25,000-gallon steel tanks.

Top

Web Hosting Directory

  • The web hosting directory is for anyone who is searching for website hosting and hosting related resources. The directory is listing Shared, VPS and Dadicated server plans in descending order for customer ratings !!! This web hosting directory is listing plans on the basis of 100% unbiased customer ratings. TheWebHostingDir.com provides you nice tool to easily search all types of web hosting plans including cheap web hosting, ASP.Net hosting, php mysql hosting, Cheap VPS Hosting, Windows VPS, HyperV VPS, Xen VPS and Cpanel VPS Hosting.